Electrical Test & Measurement

Test Equipments

Image

Since inception Ampteks, Inc. has made it a priority to acquire and maintain state-of-the art test and measurement equipment as well as vintage secondary injection test sets. All equipment that requires calibration receives NIST traceable calibration by an ISO 9001:2008 accredited calibration facility annually. Primary Injection test sets Qty 3 - 60kA, Qty 1 - 40kA, Qty 2 - 30kA, Qty 2 - 20kA, Qty 4 - 5kA, Qty 2 - 2kA

Image

Megger DDA3000

Megger DDA-3000 35,000A primary injection test set designed specifically to test low-voltage power and molded-case circuit breakers equipped with thermal, magnetic or solid-state trip devices. The unique transformer and circuit design results in a very high-capacity test set in a very compact size. Advanced digital control and instrumentation provides exact testing capacity. The test sets can also be used for other high current applications, such as verifying the ratio of current transformers and performing heat runs or primary injection testing of high-voltage breakers and their associated protective relays.

Image

Megger ODEN AT

Megger Programma ODEN AT 22,000A primary injection test set. With 208/240/480 auto transformer, the control unit has many advanced features and a powerful measurement section for example, that can display turns ratio as well as time, voltage and current. A second measurement channel can be used to measure an additional current or voltage. Current transformer turns ratio, impedance, resistance, power, power factor (cos f) and phase angle are calculated and shown in the display. Current and voltage can be presented as percentages of nominal value.

Image

Phenix HC100

Phenix Technologies HC100 100,000A primary injection test set. This powerful test set utilizes phase angle firing, a variety of test-modes and waveform display. Can be controlled with either the HC controller or PC operation.

Image

Hipotronics CBTS9600

Hipotronics CBTS9600 with MAC-21 60,000A primary injection test is a fully rated powerful test set. The MAC-21 uses proven microprocessor and A/D converter technology to provide real-time waveform analysis. Accurate true-RMS readings of current pulses, even with DC offset. Intelligent threshold algorithms provide accurate trip time measurement. Integration of measurement and control functions allow advanced features such as preset on times, auto ranging, printer or computer interface.

Image

Phenix HC5

Phenix Technologies HC5 5000A primary injection test set.

Image

AET 3kA

AET 3kA 3000A high current test set

Image

Phenix Autotransformer

Phenix Autotransformer a multiple-tap input auto transformer for 208, 240, and 575VAC operation to 480VAC.

Image

ETI AT10B

ETI AT10B Autotransformer 480VAC to 240VAC 10KVA

Image

Multi-Amp SR-98

The SR-98 is a multipurpose, lightweight, field portable test set capable of testing a wide variety of electromechanical, solid-state and microprocessor-based protective relays, small molded case circuit breakers, motor overload relays and similar protective devices.

The SR-98 incorporates a large, easy to read LCD display, which shows AC and DC Amperes, AC and DC Volts, and Time in both Seconds and Cycles. Depending on the type of test selected, other values may be displayed, such as Ohms, Watts, VARS, Phase Angle, Frequency or Power Factor. Metered quantities such as AC Amperes, AC Volts, DC Volts or DC Amperes, and Time are simultaneously displayed on the screen. The read-and-hold metering feature provides a fast and accurate preset of test values.

A relay specific test screen is included in the menu list. The user simply selects the type of relay to be tested and a test screen is provided that displays all necessary functions needed to test that particular type of relay.

Image

Megger TM200

Megger TM200 timer is trigger by voltage or current. If more than one timing cycle is to be measured timer TM200 is ideal for these tasks thanks to its precise accuracy, its broad application range and its compact dimensions. Timer.

Image

FLIR E8

Imaging and Optical Data

IR Resolution: 320 × 240

MSX Resolution: 320 × 240

Thermal Sensitivity: <0.06°C

Detector: Uncooled Microbolometer

Screen 3.0 in. 320 × 240 color LCD

Image Modes: IR image, visual image, MSX, picture-in-picture

Multi Spectral Dynamic Imaging (MSX): IR image with enhanced detail presentation

Temperature Range –4° F to 482°F (–20° to 250°C)

Alarm Blue below or red above set temperature

Emissivity Correction Variable from 0.1 to 1.0

Image

Megger TTR20

Megger TTR20-1 is an automatic, hand-held, transformer turns ratio test set.

It is used to measure the turns ratio, excitation current and polarity of windings in single- and three-phase distribution and power transformers, potential and current transformers, and tapped transformers.

Image

Megger DLRO10X

MEGGER DUCTER DLRO10X is a fully automatic instrument, selecting the most suitable test current, up to 10 A dc to measure resistance from 0.1 µO to 2000 O on one of seven ranges. DLRO 10X uses a menu system controlled by a two-axis paddle to allow manual selection of the test current. DLRO10X also adds real-time download of results and on-board storage for later download to a PC.

Image

Megger DLRO10HD

Megger DLRO10HD heavy duty low resistance ohmmeter combines rugged construction with accuracy and ease of use.

  • High or low output power selection for condition diagnosis
  • Rechargeable battery or line power supply, continuous operation, even with dead battery
  • 10 A for 60 seconds, less time waiting to cool, great for charging inductance
  • High input protection to 600 V, inadvertent connection to line or UPS voltage will not blow a fuse
  • Heavy duty case: IP 65 lid closed, IP54 operational (battery operation only)
  • Rotary switch selects one of five test modes, including auto start on connection, giving ease of use
Image

Megger MIT525

Offering CAT IV, the MIT525 is compact, light 5 kV insulation resistance tester for the diagnostic testing and maintenance of high voltage electrical equipment. Enclosed in a tough case it is both smaller and lighter than its predecessor making it even easier to carry and store.

As well as measuring insulation resistance to 10 TO, the MIT525 also offers various diagnostic tests such as Polarisation index, Dielectric Absorption Ratio, Step Voltage, Dielectric discharge and ramp testing.

Image

Vanguard VBT60

VBT-60 is a microprocessor-based 60kV dc vacuum bottle tester designed for testing circuit-breaker vacuum bottles in the field and at the shop.

Test voltages can be selected from 10 kV dc to 60 kV dc in 5 kV steps for the The high-voltage test time can be set from 5 seconds to 2 minutes. The test voltage is raised to the selected voltage and held for the test time duration. After the test time duration has elapsed and the leakage current did not pass the preset value of 100 µA, 200 µA, or 300 µA, the test voltage is returned to zero. If a flash-over condition occurs, such as bottle failure, the test voltage is immediately turned off, a “Failure” message is displayed on the LCD screen, and the “TEST FAIL” LED light on the unit is also illuminated.

Image

Doble TR3100

Doble TR3100 digital circuit breaker test system measures mechanical motion and contact performance of circuit breakers. Timing tests are performed on main contacts, resistor switches and auxiliary contacts. Other test functions include: travel and velocity measurements, measuring insertion resistor values and measuring grading capacitor values. LCD display, thermal printer.

Image

ElectoTest ITS

ElectroTest ITS Integrated Test System with 1000A current module and 60kVdc Hipot. The Model ITS control unit by itself has been designed to conveniently and accurately calibrate and test simple over-current relays, voltage relays, and other protective devices. The test set is capable of supplying 20A for 2 minutes, and 50A momentarily, AC or DC. Output voltage is adjustable to 140 VAC and 124 VDC.

Image

ElectroTest PS1

ElectroTest PS1 portable 0-480 AC and DC power supply.

Image

ElectroTest PS2

ElectroTest PS2 portable 1KVA 0-600 AC and DC power supply.

Image

ElectroTest PSDC

Phenix Technologies HC5 5000A primary injection test set.

Image

Megger DET3TC

Megger DET3 digital ground resistance meter measures ground resistance, voltage, and current for digital ground and bond testing.The DET3TC is capable of testing on-site grounds without disconnecting the utility connection. The unit measures digitally, is autoranging, and has user-selectable 25 or 50V test voltages. The noise rejection feature filters out noise up to 40V peak to peak for more accurate testing in high-noise environments. The meter measures voltage from 0 to 100V, ground current from 0.5mA to 19.9A, and ground resistance from 0.01 to 2000 ohms.

Image

Megger ICLAMP

The Megger ICLAMP current clamp is an accessory for performing (ART) attached rod technique ground resistance tests with a Megger DET4TC2, DET4TCR2, or DET3TC ground resistance tester. The clamp permits the separation of test currents in a parallel-grounded system, enabling the grounds to be tested without de-energizing the system.

Image

Utility Relay B291

Utility Relay B291 secondary injection test set is a single-phase test set designed for testing of AC-PRO microcontroller based trip units.

Image

Utility Relay B291MP

Utility Relay B291MP secondary injection test set is a single-phase test set designed for testing of AC-PRO-MP microcontroller based trip units.

Image

Eaton MTK1000

87C0270G01-G03 MTK1000 secondary injection test kit for use with MagnumDS, MagnumSB with Digitrip 520 and Digitrip 1150 series trip units. The MTK1000 supercedes the 140D481G03 test set and 8779C02G04 adapter. The MTK1000 does not require use of adapters.

Image

Eaton MTK2000

87C0270G01-G03 MTK2000 secondary injection test kit for use with MagnumDS, MagnumSB with Digitrip 520 and Digitrip 1150 series trip units. The MTK2000 supercedes the 140D481G03 test set and 8779C02G04 adapter. The MTK2000 does not require use of adapters.

Image

Eaton OPTIMizer

Qty 3 on hand

7801C57 OPTIMizer Hand Held Programmer is required for all OPTIM Trip Unit Systems. It plugs into the front of OPTIM 550, 750 or 1050 Trip Units and is powered by a standard nine volt battery or auxiliary power module. The OPTIMizer accesses, displays, and configures information from OPTIM Trip Units. The OPTIMizer Hand Held Programmer provides a broad range of programming possibilities available with the OPTIM Trip Unit System and the range of compatible circuit breakers.

Image

Eaton STK2 1232C50G10

Qty 3 on hand

Eaton STK-2 1232C50G10 secondary injection test set for Seltronic and Digitrip 310 Trip Units. Supercedes 1232C50G05

Image

Westinghouse 1287C56G02

1287C56G02 secondary injection test set for Seltronic trip units.

Image

Eaton 140D481G04

Qty 3 on hand

Eaton Cutler Hammer 140D481G04 secondary injection test set for DS, DSII, MagnumDS Breakers. Amptector trip units require no adaptor, Digitrip 500 thru 800 and 510 thru 910 require the 8779C02G03 adaptor, while the Digitrip 520 and 1150 require the 8779C02G04 adaptor.

Image

Westinghouse 140D481G03

Qty 2 on hand

Westinghouse 140D481G03 secondary injection test set for DS, DSII, MagnumDS Breakers. Amptector trip units require no adaptor, Digitrip 500 thru 800 and 510 thru 910 require the 8779C02G03 adaptor, while the Digitrip 520 and 1150 require the 8779C02G04 adaptor.

Image

Westinghouse 140D481G02RR

Westinghouse 140D481G02RR secondary injection test (RR=factory modified for use with Digitrip microprocessor based trip units) set for DS, DSII, MagnumDS Breakers. Amptector trip units require no adaptor, Digitrip 500 thru 800 and 510 thru 910 require the 8779C02G03 adaptor, while the Digitrip 520 and 1150 require the 8779C02G04 adaptor.

Image

Westinghouse 140D481G02

Westinghouse 140D481G02 secondary injection test set for DS breakers with Amptector trip units only, no adaptor required.

Image

Eaton 8779C02G03

Qty 3 on hand

Eaton Cutler Hammer 8779C02G03 DS / DS II Adaptor for 140D481Go3 DS, DSII Test Kit for Digitrip 510, 610, 810, 910 Trip Units

Image

Eaton 8779C02G04

Qty 2 on hand

Eaton Cutler Hammer 8779C02G04 Magnum DS Test Kit Adapter For use with 140D481G03 or 140D481G04 Test kit for Digitrip 220, 520, 1150 Trip Units. 8779C02G04 converts the 11-pin banana plug on the 140D481G04 test set, to a 14-pin plug. This 14-pin plug, plugs into the trip unit test port located on the face of the trip unit.

Image

Eaton PRTBAPMDV

Qty 5 on hand

Eaton’s Auxiliary Power Module is an intermittent duty device specifically used to power up the Digitrip family of trip units. This permits easy bench testing and field testing of the trip units as well as displaying data, settings and the initial configuring of communication address and baud rates. Additionally, the module will power an OPTIMizer handheld programmer.

Image

Cutler Hammer PRTAAPM

Auxiliary Power Module for Cutler Hammer 140D481G03 Test Kit to test Digitrip RMS 510, 610, 810 and 910 Trip Units.

Image

Westinghouse 1278C67G01

Westinghouse 1278C67G01 portable test kit for field testing and calibration of all plug-incards and output relays. The only power source required is a 120V convenience outlet.

A selector switch allows the operator to test individual cards or to simulate ATS operation by having the source monitoring cards drive the time delay cards which in turn drive the output relays, exactly as in actual use. Calibration checks or changes can thus be accomplished without necessity of energizing the alternate power source.

Image

Carriere STS100

Carriere STS100 secondary injection test set for Carriere retrofit kits with DIGITAL 600 or FB600E/ER trip unit.

Image

GE GTUTK20

Qty 4 on hand

Secondary Injection Test kit for EntelliGuard TU Trip Units

Image

GE TVRMS2

Qty 5 on hand

GE TVRMS2 secondary injection test set for RMS9, MVT+, MVT PM trip units.

Image

GE TAKTS2

GE TAK-TS2 secondary injection test set for ECS/SST and versatrip mod.2 trip units

Image

GE TVTS1

Qty 3 on hand

GE TVTS1 secondary injection test Set for MicroVersaTrip Trip Units

Image

GE PST1-1A

GE PST1-1A 0102D2526G10 secondary injection test set for Power Sensor trip units.

Image

Merlin Gerin 34547

Merlin Gerin 55391 34547 MasterPact secondary injection test set for Trip Units STR18-STR58U ST208-ST418 STR25-STR55UP STCM2 and STCM3 ST204-ST224 ST205-ST315 Compact NS Trip Units STR22, STR23, STR22ME, STR43, STR53

Image

Merlin Gerin 685386A

Merlin Gerin 685386A secondary injection test kit for CM circuit breakers with ST306, ST608 trip units. Includes 677928 CM test plug, 648848 W test plug.

Image

ABB PR030/B

Qty 3 on hand

PR030/B BATTERY UNIT FOR PR121-PR122-PR123-PR232-PR33x E1/6-T7-T7M-X1-T8

Image

Allis Chalmers PTS2

Allis Chalmers PTS2 18-468-400-501 secondary injection test kit for Allis Chalmers / Siemens LA frame with Static Trip I or Static Trip II trip units.

Image

Siemens PTS4

Siemens PTS-4 secondary injection test set for LA and RL frames with Static Trip I, Static Trip II and Static Trip III trip units.

Image

Siemens TS31

Qty 2 on hand

Siemens TS-31 secondary injection test set for Sensitrip III, and SB Breakers

Image

Siemens WLTS

3WL9111-1AT31-0AA0 Hand Held test device for WL Breakers ETU trip Units. The test device is used to verify the proper operation of the trip unit, the energy transformers and current transformers as well as the tripping solenoid F5 and the measured value display.

Image

Square D S55594

Qty 5 on hand

Square D S33594 Hand Held Test Kit for Micrologic 7.0H, 7.0P, 7.0A, 6.0H, 6.0P, 6.0A,-5.0H, 5.0P, 5.0A, 5.0, 3.0A, 3.0, 2.0A, 2.0, ET1.0l, ET1.0M, STR53, STR43, STR23, STR22 Includes: Square D S33937 Primary Injection Adapter, S48907 7pin test cable

Image

Square D S33595

Square D S33595 Full Function Test Kit v1.10 for Micrologic 7.0H, 7.0P, 7.0A, 6.0H, 6.0P, 6.0A,-5.0H, 5.0P, 5.0A, 5.0, 3.0A, 3.0, 2.0A, 2.0, ET1.0l, ET1.0M, STR53, STR43, STR23, STR22

Image

Square D UTS3

Qty 2 on hand

UTS3 Universal Test Set is designed to perform operational tests and diagnoses of Square D electronic trip circuit breakers with Micrologic Series B trip units, circuit breaker components and tripping functions.

Includes: CBTMB Series B Module, Series B adapter, CBTMT self test module